|本期目录/Table of Contents|

[1]周朝霞,叶晓江.大空间应用新风换气机加风机盘管的节能分析[J].武汉工程大学学报,2013,(12):79-82.[doi:103969/jissn16742869201312016]
 ZHOU Zhao\|xia,YE Xiao\|jiang.Energy saving evaluation and analysis of fresh air ventilator plus fan coil applied in large space[J].Journal of Wuhan Institute of Technology,2013,(12):79-82.[doi:103969/jissn16742869201312016]
点击复制

大空间应用新风换气机加风机盘管的节能分析(/HTML)
分享到:

《武汉工程大学学报》[ISSN:1674-2869/CN:42-1779/TQ]

卷:
期数:
2013年12期
页码:
79-82
栏目:
机电与信息工程
出版日期:
2013-12-31

文章信息/Info

Title:
Energy saving evaluation and analysis of fresh air ventilator plus fan coil applied in large space
文章编号:
16742869(2013)12007904
作者:
周朝霞叶晓江
武汉工程大学理学院,湖北 武汉 430074
Author(s):
ZHOU Zhao\|xiaYE Xiao\|jiang
School of Science,Wuhan Institute of Technology,Wuhan 430074,China
关键词:
大空间全热回收新风换气机风机盘管节能
Keywords:
large space total heat reclaim fresh air ventilator primary fan coil system energy saving
分类号:
TB567.2
DOI:
103969/jissn16742869201312016
文献标志码:
A
摘要:
公共建筑的电耗已接近城市建筑电耗的50%,而空调能耗占建筑能耗的33%~45%.大空间是公共建筑的特点,减少大空间的能耗是降低公共建筑能耗的关键.大空间按照规范设计一般是采用全空气空调系统,为了提高大空间节能效果,应针对不同大空间采用不同空调系统.对于体型复杂,空间大小不规则,空间高度大于5 m以上的大空间仍采用常规一次回风(无再热)全空气系统;对于体型比较规整,房间吊顶净高在4 m左右的大空间宜采用新风换气机加风机盘管空调系统.通过对武汉450 m2大空间,净高4 m的办公室应用新风换气机加风机盘管系统的夏季工况分析,对照常规一次回风(无再热)全空气系统,证实新风换气机加风机盘管系统节能效果显著,全热回收装置节能42.84%,且当室外设计参数朝着温度降低、相对湿度增加的方向变化时,节能效果及室内参数将朝着有利于全热回收的方向发展.
Abstract:
The electricity consumption of public building has almost reached 50% electricity consumption of city building, and the air\|conditioning energy consumption reaches 33% to 45% of building energy consumption. Large space is the common feature of public building, so reducing energy consumption in large space is the key to drop energy consumption of public building. Large space normally utilizes all\|air air conditioning system according to the code of design. To improve the energy saving effect in large space, various air\|conditioning system should be applied when facing different types of large space. In case of the large space with complicated shape, irregular space and the height of space over 5 m, the normal all\|air primary return air system(without re\|heating) should be applied; in case of the large space with regular shape and clear room height of approximately 4 m, the fresh air exchanger plus fan\|coil\|air\|conditioning system is preferred. Furthermore, through analyzing the summer working conditions of fresh air ventilator and primary fan coil system in a spacious office with clear height of 4 m and area of 450 m2 at Wuhan, the combination of fresh air ventilator and primary fan coil system is proved to have significant effect on saving energy: the energy savings of total heat reclaim unit is 42.84%. Furthermore, when outdoor design parameters changes toward the direction of lowering the temperature and increasing the relative humidity, the efficiency of saving energy and indoor parameters will become more beneficial towards the total heat reclaim model.

参考文献/References:

[1]王远,魏庆芃,薛志峰,等.大型公建节能会诊(三)——调查分析篇大型公建建筑能耗调查分析[J].建设科技,2007(2):17\|19.  WANG Yuan, WEI Qing\|peng, XUE Zhi\|feng, et al. Large scale public building conference (Ⅲ)\| Investigation section of large scale public building energy consumption investigation[J]. Building Technology,2007(2):17\|19.(in Chinese)[2]何华,周智勇,龙天渝,等.重庆市江北区公共建筑能耗调研[J].燃气与热力,2009,29(10):A22\|A26.  HE Hua, ZHOU Zhi\|yong, LONG Tian\|yu, et al. Energy consumption investigation of public building in jiang bei section of chong qing city[J].Combustion Gas and Thermodynamic, 2009,29(10):A22\|A26.(in Chinese) [3]赵国庆.大空间建筑空调设计概述[J].低温与特气,2007,25(5):7\|9. ZHAO Guo\|qing. Summary of large space building air\|conditioning design[J].Low Temperature and Special Gas,2007,25(5):7\|9.(in Chinese)[4]李向东.住宅空调系统设计与室内空气质量研究[D].西安:西安建筑科技大学,2004. LI Xiang\|dong. Design of residence air\|conditioning system and quality research of indoor air [D]. Master Thesis of Xian Building Technology University,2004.(in Chinese)[5]北京节能环保节能服务中心.大型公建节能读本[M].北京:经济日报出版社,2006. Beijing energy saving and environment protection service center. Large scale public building energy saving book[M]. Beijing: Economic Daily Press, 2006.(in Chinese)[6]周祖毅.基于大流量、大空间空调系统设计及运行不合理现象的思考[J].制冷空调与电力机械,2010,31(6):62\|66. ZHOU Zu\|yi. Thought on design of large space air\|conditioning system design and unreasonable phenomenon based on large scale human flow[J].Refrigeration Air\|conditioning and Electric Power Machinery,2010,31(6):62\|66.(in Chinese) [7]中华人民共和国建设部.GB50019\|2003,采暖通风与空气调节设计规范[S].北京:中国计划出版社,2003. Construction department of The People’s Republic of China.GB50019\|2003 The code for design of heating ventilation and air conditioning[S].Beijing: China Planning Press, 2003.(in Chinese) [8]中华人民共和国建设部.GB50189\|2005 公共建筑节能设计标准[S].北京:中国建筑工业出版社,2005.Construction department of The People’s Republic of China.GB50189\|2005 The code for energy saving design of public building[S].Beijing: China Architecture and Building Press, 2005.(in Chinese)

相似文献/References:

备注/Memo

备注/Memo:
收稿日期:20130225基金项目;2007年湖北省建设科技研究项目作者简介:周朝霞(1961\|),女,江苏江阴人,副教授.研究方向:空气源热泵、地面辐射采暖、人工环境、温湿度独立控制.
更新日期/Last Update: 2014-01-07